Connector-ready cooling units, which is ready for immediate use. Mounted directly on top of the morgue. The units have a sturdy housing with low-noise emittance, are fully thermal, and equipped with an air-cooled compressor. The safety utilities are in accordance with EN (DIN) standards, VDE regulations and VBG guidelines. Also included is a high-capacity evaporator with automatic defrosting, an electrical temperature regulation and a digital temperature indicator with connection and protective plug.
Temperature range: Voltange: Refrigeration capacity 0°C inside, +40°C outside: Rated Input (when normally running): Rated input: Peak current: Max. current: Defrost: Weight: Filling quantity refrigerant: Compressor: Type: Normal power: Condenser: Air flow: Evaporator: Air flow: Air throw: Dimensions W/D/H: Dimensions opening L/W: Type: Article No.: | +10°C to -5°C 230 V / 1 Ph / 50 Hz 753 Watt 800 Watt 4.7 Amp 26 Amp 7.8 Amp hot gas defrosting 42 kg 0.47 kg hermetic 500 Watt 400 m³/h 500 m³/h 3 m (Standard) 430 x 771 x 378 mm 355 x 306 mm KT 80 - R 134A 040.100.104 |